Accessory input, Communication port, Contact input circuits – Basler Electric DECS-100 User Manual
Page 15: Common alarm output, Field output, Avr operating mode, Accessory input -3, Communication port -3, Contact input circuits -3, Common alarm output -3

9287500991 Rev M
DECS-100 General Information
1-3
Accessory Input
Voltage Range:
–3 Vdc to +3 Vdc
Setpoint Range:
–30% to +30% shift
Burden:
1 k
Ω
Terminals:
A, B
Communication Port
Interface:
Full duplex RS-232
Connection:
Rear panel DB-9 connector
Baud:
4800
Data Bits:
8
Parity:
None
Stop Bit:
1
Contact Input Circuits
Type:
Dry contacts
Interrogation Voltage:
13 Vdc (supplied by DECS-100)
Terminal Assignments for Standard Functions
Raise:
6U, 7
Lower:
6D, 7
Var/PF Enable:
52J, 52K
Parallel Control:
52L, 52M
Voltage Matching:
VM, VMC
Common Alarm Output
Type:
Form A
Rated Load:
7 Aac/Adc continuous
Make:
30 Aac/Adc, carry for 0.2 sec
Break:
7 Aac/0.1 Adc
Operating Voltage:
240 Vac/250 Vdc maximum
Terminals:
AL1, AL2
Field Output
Continuous Rating:
63 Vdc, 7 Adc
Field Resistance:
9
Ω minimum
Terminals:
F+, F–
10 Second Forcing Rating
200 Vac Power Input:
135 Vdc, 15 Adc
110 Vac Power Input:
90 Vdc, 10 Adc (9
Ω field)
75 Vdc, 15 Adc (5
Ω field)
AVR Operating Mode
Adjustment Range:
See Generator Voltage Sensing
Voltage Regulation:
±0.25% over load range at rated power factor and constant generator
frequency.
±0.5% with 3-phase sensing and shunt power at 40% THD of the voltage
waveform (due to a six SCR load).
Temperature Drift:
±0.5% for a 40
°C change
V/Hz Characteristic:
Slope from 0 to 3PU is adjustable in 0.01PU increments. Transition
(Corner) frequency is adjustable from 40 to 65 Hz. See Figure 1-2 for the
V/Hz curves.
Response Time:
Within 1 cycle