Specifications, Operating power, Generator voltage sensing – Basler Electric DECS-100 User Manual
Page 14: Generator current sensing, Bus voltage sensing (optional), Specifications -2, Operating power -2, Generator voltage sensing -2, Generator current sensing -2, Bus voltage sensing (optional) -2

1-2
DECS-100 General Information
9287500991 Rev M
Style Number Example
For example, a DECS-100 with a style number of A15 would have the following characteristics and
operating features.
A ------- No var or power factor control
1 -------- Voltage matching
5 -------- 5 ampere current sensing
SPECIFICATIONS
DECS-100 specifications and qualifications are listed in the following paragraphs.
Operating Power
Refer to Section 4, Installation for special requirements concerning the application of operating power
during DECS-100 programming and the application of station power.
Voltage:
88 to 250 Vac, single-phase or three-phase (L-L)
Frequency:
50 to 400 Hz
Power Dissipation:
40 W (maximum continuous)
Burden:
650 VA
Voltage Buildup:
≥6 Vac
Terminals:
3, 4, 5
Generator Voltage Sensing
Type:
1-Phase/3-Phase, 4 ranges
Burden:
<1 VA per phase
Terminals:
E1, E2, E3
50 Hertz Sensing
Range 1:
100 Vac (85 to 132 Vac)
Range 2:
200 Vac (190 to 220 Vac)
Range 3:
400 Vac (380 to 440 Vac)
Range 4:
N/A
60 Hertz Sensing
Range 1:
120 Vac (85 to 132 Vac)
Range 2:
240 Vac (170 to 264 Vac)
Range 3:
480 Vac (340 to 528 Vac)
Range 4:
600 Vac (540 to 660 Vac)
Generator Current Sensing
Type:
1-phase (B-phase), 50/60 Hz
Style XX1:
1 Aac maximum continuous
Style XX5:
5 Aac maximum continuous
Burden:
<0.1 VA
Terminals:
CT1, CT2
Bus Voltage Sensing (Optional)
Type:
1-phase, 4 ranges
Burden:
<1 VA per phase
Terminals:
B1, B3
50 Hertz Sensing
Range 1:
100 Vac (85 to 132 Vac)
Range 2:
200 Vac (190 to 220 Vac)
Range 3:
400 Vac (380 to 440 Vac)
Range 4:
N/A
60 Hertz Sensing
Range 1:
120 Vac (85 to 132 Vac)
Range 2:
240 Vac (170 to 264 Vac)
Range 3:
480 Vac (340 to 528 Vac)
Range 4:
600 Vac (540 to 660 Vac)