Figure 1-2. percentage restraint characteristic, Table 1-1. multiples of tap, O table 1-1 and figure 1-2. table 1-1 – Basler Electric BE1-87T User Manual
Page 18: N figure, N figure 1-2

1-6
BE1-87T General Information
9171300990 Rev V
Table 1-1. Multiples of Tap
Front Panel Setting %
15
20
25
30
35
40
45
50
55
60
Maximum Restraint
Current At Minimum
Pickup In Multiples of
Tap
2.33 1.75 1.40 1.17 1.00 0.875 0.778 0.700 0.636 0.583
Figure 1-2. Percentage Restraint Characteristic
Second-Harmonic Restraint Inhibit of the restrained output occurs when the second-
harmonic component exceeds a pickup setting which is 12%
of the operating current for single-phase units or 18% for
three-phase units.
Fifth-Harmonic Restraint
Inhibit of the restrained output occurs when the fifth-harmonic
component exceeds a pickup setting which is 35% of the
operating current.
Unrestrained Output
Pickup Range
Front panel thumbwheel switches adjust the pickup point of
the unrestrained output over a range of 6 to 21 times the tap
setting in increments of 1 x Tap.
Pickup Accuracy
±
3% of the front panel setting.