5-6
BE1-87T Test Procedures
9171300990 Rev V
Check:
Therefore: Use Equation 3 or 3a.
From Figure 1-2 (the percentage restraint characteristic of the BE1-87T at 15% slope), the minimum
current where trip occurs is:
In terms of current, the trip current is:
Using Equation 3a:
(
)
I
trip
2
1 015 6 38
2
9 69
= −
× ×
=
.
.
. A
NOTE
The relay operates on maximum restraint. By reducing the current of one input,
the published trip/non-trip regions are as defined by Figure 1-2.
I balance
slope
2
0 35
100
< >
(in pu)
3 < 2.333
.
0 35
0 15
3 < >
.
.
)
(
I trip
2
3 pu (1 - 0.15)
= 2.55 pu
=
I trip
2
2.55 pu (Tap)
= (2.55) (3.8)
= 9.69 A 6% 100 mA
=
±
±
See also other documents in the category Basler Electric Relay:
- BE1-11i RTD Module (672 pages)
- BE1-11m Terminals and Connectors (604 pages)
- BE1-11i RTD Module (554 pages)
- BE1-11 DNP3 Protocol (82 pages)
- BE1-11 IEC 61850 Protocol (100 pages)
- BE1-11 Modbus Protocol (186 pages)
- BE1-851 (364 pages)
- BE1-851E DNP3 Protocol (40 pages)
- BE1-851E Modbus Protocol (70 pages)
- BE1-700 (460 pages)
- BE1-700 Modbus Protocol (92 pages)
- BE1-50 (44 pages)
- BE1-50/51B (76 pages)
- BE1-50/51M (74 pages)
- BE1-50/51B-122 (66 pages)
- BE1-50/51B-232 (64 pages)
- BE1-50/51B-231 (60 pages)
- BE1-50/51B-233 (60 pages)
- BE1-50/51B-240 (52 pages)
- BE1-50/51B-241 (52 pages)
- BE1-50/51B-244 (64 pages)
- BE1-50/51B-225 (72 pages)
- BE1-50/51B-228 (68 pages)
- BE1-50/51B-226 (52 pages)
- BE1-50/51B-236 (68 pages)
- BE1-50/51B-239 (76 pages)
- BE1-50/51B-238 (70 pages)
- BE1-51 (100 pages)
- BE1-64F (30 pages)
- BE1-51/27C (112 pages)
- BE1-25 (66 pages)
- BE1-51/27R (114 pages)
- BE1-87G (68 pages)
- BE1-59N (40 pages)
- BE3-25 (2 pages)
- BE3-27T/59T (2 pages)
- BE3-27/59 (2 pages)
- BE3-32 (2 pages)
- BE1-32O/U (82 pages)
- BE3-47 (2 pages)
- BE3-37/51 (2 pages)
- BE3-47N/27 (2 pages)
- BE3-49R-3 Inputs (2 pages)
- BE3-49R-6 Inputs (2 pages)
- BE3-49TL (2 pages)