Response time verification, Response time verification -13, Table 5-4. timing: 5 a, 50 or 60 hz – Basler Electric BE1-87T User Manual
Page 109

9171300990 Rev V
BE1-87T Test Procedures
5-13
Response Time Verification
Step 1. Connect the relay as appropriate (refer to Figures 5-1 through 5-4).
Step 2. Set the RESTRAINED PICKUP LEVEL switch (phase A) to A (15%). Place all of the INPUT
switches on the 2.0 A tap position.
Step 3. Apply 2.0 A at 50 or 60 Hz, as appropriate for the style, to Input 1 (terminals 11 & 13 on both
single- and three-phase styles) and to Input 2 (terminals 12 & 13 on Single-Phase and
terminals 15 & 18 on three-phase).
Step 4. Perform a restrained trip at 2 x Pickup by stepping the Input 2 current 3.4 A. Note the time
interval between initiation of the simulated fault and the closure of the restrained output contact.
The trip time should be less than that shown in Table 5-4.
Step 5. Repeat Step 4 at I
OP
= 10 x Pickup. Note that, with Input 1 at 2.0 A, Input 2 current should be
stepped to 9.0 A. The trip time should be less than that shown in Table 5-4.
Step 6. Three-Phase Units Only: Repeat Steps 1 through 5 for Phases B and C.
Step 7. Place the UNRESTRAINED PICKUP LEVEL switch to the A setting (6 X TAP). Place all of the
INPUT switches to the 2.0 A tap position.
Step 8. With 0.0 A at Input 1 (terminals 11 & 13), apply 24 A (2 x Pickup) to Input 2 (terminals 12 and
13 on single-phase and terminals 15 & 18 on three-phase). Note the time interval between
initiation of the simulated fault and the closure of the unrestrained output contact. The interval
should be less than that shown in Table 5-4.
Step 9. Repeat Steps 7 and 8 at 10 x Pickup. Note that, with Input 1 at 0.0 A, it will be necessary to
step the Input 2 current to 120.0 A for an unrestrained trip. The trip time should be less than
that shown in Table 5-4.
Step 10. Three-Phase Units Only: Repeat Steps 8 and 9 for phases B and C.
Table 5-4. Timing: 5 A, 50 or 60 Hz
Function
Differential Current
Option 1-0
Timing Maximum
Option 1-1
Timing Maximum
50 Hz
60 Hz
50 or 60 Hz
Restrained Trip
2 x Pickup
81 ms
70 ms
49 ms
Restrained Trip
10 x Pickup
73 ms
67 ms
37 ms
Unrestrained Trip
2 x Pickup
70 ms
57 ms
57 ms
Unrestrained Trip
10 x Pickup
32 ms
28 ms
10 ms