Conclusion – Basler Electric BE1-87T User Manual
Page 138

A-10
BE1-87T Setting Notes
9171300990 Rev V
Figure A-10. Comparing SF and SF`
Figure A-11 illustrates how a lower Rs value reduces the difference between SF and SF`.
Figure A-11. Reducing the Difference between SF and SF’
Conclusion
This analysis shows that the easy to apply SF based on the ANSI Accuracy Class may yield optimistic
results in cases where the CT internal resistance is significant. The Excitation curve method, requiring
more data, yields more accurate results and should be used when the SF is marginal.
SFIF
SF'IF
IF
0
20
40
60
80
100
0
0.2
0.4
SF and SF` for Zc=2, ZB=0.5, Rs=0.2
SFIF
SF'IF
IF
0
20
40
60
80
100
0
0.2
0.4
SF and SF` for Zc=2, ZB=0.5, Rs=0.2
See also other documents in the category Basler Electric Relay:
- BE1-11i RTD Module (672 pages)
- BE1-11m Terminals and Connectors (604 pages)
- BE1-11i RTD Module (554 pages)
- BE1-11 DNP3 Protocol (82 pages)
- BE1-11 IEC 61850 Protocol (100 pages)
- BE1-11 Modbus Protocol (186 pages)
- BE1-851 (364 pages)
- BE1-851E DNP3 Protocol (40 pages)
- BE1-851E Modbus Protocol (70 pages)
- BE1-700 (460 pages)
- BE1-700 Modbus Protocol (92 pages)
- BE1-50 (44 pages)
- BE1-50/51B (76 pages)
- BE1-50/51M (74 pages)
- BE1-50/51B-122 (66 pages)
- BE1-50/51B-232 (64 pages)
- BE1-50/51B-231 (60 pages)
- BE1-50/51B-233 (60 pages)
- BE1-50/51B-240 (52 pages)
- BE1-50/51B-241 (52 pages)
- BE1-50/51B-244 (64 pages)
- BE1-50/51B-225 (72 pages)
- BE1-50/51B-228 (68 pages)
- BE1-50/51B-226 (52 pages)
- BE1-50/51B-236 (68 pages)
- BE1-50/51B-239 (76 pages)
- BE1-50/51B-238 (70 pages)
- BE1-51 (100 pages)
- BE1-64F (30 pages)
- BE1-51/27C (112 pages)
- BE1-25 (66 pages)
- BE1-51/27R (114 pages)
- BE1-87G (68 pages)
- BE1-59N (40 pages)
- BE3-25 (2 pages)
- BE3-27T/59T (2 pages)
- BE3-27/59 (2 pages)
- BE3-32 (2 pages)
- BE1-32O/U (82 pages)
- BE3-47 (2 pages)
- BE3-37/51 (2 pages)
- BE3-47N/27 (2 pages)
- BE3-49R-3 Inputs (2 pages)
- BE3-49R-6 Inputs (2 pages)
- BE3-49TL (2 pages)