Vent Requirements

!

The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas
appliance must use it's own separate vent system.

!

Make sure the exhaust pipe (the inner pipe) on the heater connects to the exhaust portion of the cap
(the inner pipe). The illustrations below show how the flex liners should be attached.

!

If the heater is
installed at an
altitude over 3,000
(1,000 M) feet the
flame quality will
need to be carefully
evaluated. See
Addendum #1,
"Altitude
Considerations", on
page 49.

?

When using flexible
gas vent, do not
crimp or rupture the
liner when bending it
into chimney offsets

When installed, the
vent must meet all of
the vent
manufacturer's
requirements

+

There are two
options for vent
installation:

Flex Re-Line
(Full Re-Line or Exhaust
Only Re-Line):

• Appliance Connector

(Part # 923TCL)

• 3" (75 mm) Listed

B-vent liner

• Termination Kit

(part # 923GK).

• Vertical Termination

(part # 991)

• Block-Off Plate

Co-Axial & Flex:

• Appliance Connector

(Part # 923TCL)

• 3" (75 mm) Listed

B-vent liner

• Block-Off Plate

• Termination Kit

(part # 923GK).

• Dura-Vent Co-Axial Vent and

Cap (see pg 8 for part #'s).

Z.C. (Metal) firebox

Zero Clearance
(Metal) Fireplace

Masonry
Fireplace

Direct Vent Cap

(part # 991)

High-Temp.

Silicone

Seal the adapter to the
heater with high-
temperature silicone
(seal the outside only)

Optional Block-Off Plate
(non-combustible)

High-Temp.

Silicone

Apply high-temperature
silicone to the 3" (75
mm) outlets on both
adapter boxes. Install
the flex duct and secure
with 2 screws.

3" (75 mm)

Listed

B-vent liner

High-Temp.

Silicone

Dura-Vent Termination Kit

(part # 923GK)

Dura-Vent Appliance

Connector (Part # 923TCL)

Exhaust Only

Re-Lines

You may terminate the inlet
above the a block-off plate
that is sealed air-tight to the
walls of the fireplace and to
the vents
. Combustion air is
then drawn down the
chimney. Any cracks or
damage inside the chimney
must be repaired.

Z.C. (Metal)

firebox

Zero Clearance
(Metal) Fireplace
(may be used
with a masonry
fireplace as well)

Apply high-temperature
silicone to the 3" (75 mm)
flex duct at both ends.
Install the flex duct and
secure with 2 screws.

Direct Vent

Sections

Seal the adapter box to the heater
with high-temperature silicone
(seal the outside only)

Co-Axial Vent Re-Line

High-Temp.

Silicone

Block-Off Plate
(non-combustible)

Optional cover plate

to keep rain out.

Apply a 1/8" (3 mm)
bead of high-
temperature silicone
to the inner pipe.
The silicone must
seal the inner pipe
from the outer pipe.

High-Temp.

Silicone

Direct Vent Cap

(part # 991)

3" (75 mm)

Listed

B-vent liner

High-Temp.

Silicone

Dura-Vent Termination Kit

(part # 923GK)

Dura-Vent Appliance

Connector (Part # 923TCL)