- For Qualified Installers Only!

Vent Requirements

!

Always maintain the required 1" clearance (air space) to combustible materials to prevent a fire
hazard. Do not fill air spaces with insulation.

!

The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas
appliance must use it's own separate vent system.

!

If the stove is installed at an
altitude over 3,000 feet
(1,000 M) the flame quality
will need to be carefully
evaluated. See Addendum
#1, "Altitude
Considerations", on page 38.

When the vent passes through
a wall, a wall thimble is
required. When the vent
passes through a ceiling, a
support box or firestop is
required. When the vent
passes through the roof, a
roof flashing and storm collar
are required. Follow the
instructions provided with the
vent (from Duravent®) for
installing these items.

Use a firestop spacer whenever
passing through a ceiling
(Duravent Part #963)

Vertical Termination
(Duravent Part # 991)

Use a roof flashing and storm collar
whenever passing through the roof
(Duravent Part #953 & #943 or #943S)

8-5/8"

(220 mm)

Use a support box
on exposed vent

Vertical Vent

Requirements

Use a wall thimble
whenever passing
through a wall
(Duravent Part #942)

Horizontal Termination
(Duravent Part #984)

Maintain a minimum 1" (25 mm)
clearance from vent to any combustible
(vent is 6 5/8" (170 mm) diameter)

Minimum
Framing for
wall thimble

Horizontal Vent

Requirements

Minimum framing
for fire stop

8-5/8"

(220 mm)

Maintain a minimum 1"
(25 mm) clearance from
vent to any combustible
(vent is 6 5/8" (170 mm)
diameter)

Use Model GS Direct Vent manufactured by Simpson Dura-Vent

only

(or the Chimney Conversion

Kit - see Addendum #2). Follow the installation instructions included with the vent. For the nearest
Simpson Dura-Vent supplier, call (800) 835-4429. Part numbers and descriptions are listed below.
Straight Lengths

908B

6" Pipe Length, Black (interior)

907B

9" Pipe Length, Black (interior)

906

12" Pipe Length, Galvanized

906B

12" Pipe Length, Black (interior)

904

24" Pipe Length, Galvanized

904B

24" Pipe Length, Black (interior)

903

36" Pipe Length, Galvanized

903B

36" Pipe Length, Black (interior)

902

48" Pipe Length, Galvanized

902B

48" Pipe Length, Black (interior)

911B

11" to 14 5/8" Pipe, Adjustable, Black (interior)

Vent Terminations

981

Snorkel Termination (36" rise)
(for basement or raised
termination installations)

982

Snorkel Termination (14" rise)
(for basement or raised
termination installations)

984

Horizontal Square Termination

950

Vinyl Siding Standoff

991

Vertical Termination

Elbows

990

90• Elbow

990B

90• Elbow, Black (interior)

945

45

°

Elbow

945B

45

°

Elbow, Black (interior)

Penetration, Support Parts

942

Wall Thimble

941

Cathedral Ceiling Support Box

943

Flashing, 0/12 to 6/12 Roof Pitch

943S

Flashing, 7/12 to 12/12 Roof Pitch

953

Storm Collar

963

Ceiling Firestop

988

Wall Strap

Apply high-temperature silicone to the male section of inner
pipe (on the upper section of vent) so the silicone seals the
inner pipe from the outer pipe when the sections are
assembled. Slide the sections together and turn 1/4 turn until
the sections lock in place. Install three metal screws through
each joint to lock the outer section in place (see the
instructions included with the vent for further details).

Horizontal sections require a 1/4" rise every 12" of travel

+

Exterior Vent Diameter = 6-5/8", Inner Vent Diameter = 4"

Apply a 1/8" (3 mm)
bead of high-
temperature silicone
to the inner pipe.
The silicone must
seal the inner pipe
from the outer pipe.

Silicone

Horizontal sections require non-combustible support every three feet (e.g.: plumbing tape)

Seal the inner vent to the appliance.