TOVE

I

NSTALLATION

(

CONT

.)

- For Qualified Installers Only!

Floor Protection Requirements

When the stove is installed directly on carpeting, vinyl or other combustible material other than
wood flooring, the stove must be installed on a metal or wood protection panel extending the full
width and depth of the pedestal (Minimum 24-1/2" (622 mm) wide by 20" (508 mm) deep).

Stove Placement Requirements

Heater must be installed on a level surface capable of supporting the heater and vent

Due to the high temperature of the heater, it should be located out of traffic and away from furniture
and draperies. Heater must be placed so no combustibles are within, or can swing within 36" (910
mm) of the front of the heater (e.g. drapes, doors)

?

When placed in a location where the floor to ceiling height is under 7 feet (2130 mm), the
installation is considered an alcove and must meet the following requirements:

The alcove floor to ceiling height must be at least 58" (1470 mm) tall

The alcove must not be more than 48" (1220 mm) deep before the ceiling returns to 7' (2130 mm)

The alcove must be at least 44-1/2" (1130 mm) wide

The stove must not be placed so the vents below or above the door, along the sides of stove, or along
the back of the heater can become blocked.

Minimum Clearances

10" Min.

(254 mm)

3" Min.
(76 mm)

When installed with
this clearance, the
vent is 4-1/4" (108
mm) from the back
wall, 19" (483 mm)
from the side wall.

45°

Straight Installations

Corner Installations

When installed with
this clearance, the
vent is 12-3/4" j(324
mm) from the wall.

4" Min.
(102 mm)