Approved Venting Configurations with a Horizontal Termination
•
A Minimum of 2' (.5 M) rise is required directly off of the stove
•
A minimum of 1' (.3 M) run is required
•
If using a Snorkel Termination (14"[.4 M] or 36" [.9 M]) add the snorkel height to the vertical
height.
•
The termination must fall withinin the shaded area shown in the chart. Use the indicated restrictor
position.
5' (min.)
(1.5 M)
0 feet
11' (max)
(3.4 M)
5 feet
(1.5
M)
0 feet
5 feet
(1.5
M)
12'(max)
(3.7 M)
0 feet
0 feet
NOTE:
Horizontal sections require a 1/4" (6 mm) rise every 12" (300 mm) of travel.
12'(max)
(3.7 M)
NOTE:
Restrictor positions
are based upon lab
tests. The ideal
restrictor position may
vary slightly,
especially when the
termination is near a
demarkation line.
Restrictor
Position # 5
NOTE:
A minimum 2' (.5 M) rise is
required directly off of the stove.
NOTE:
A minimum 1' (.3 M)
horizontal run is required.
Restrictor
Position # 1
5' (min.)
(1.5 M)
11' (max)
(3.4 M)