Approved Venting Configurations with a Horizontal Termination

A Minimum of 2' (.5 M) rise is required directly off of the stove

A minimum of 1' (.3 M) run is required

If using a Snorkel Termination (14"[.4 M] or 36" [.9 M]) add the snorkel height to the vertical
height.

The termination must fall withinin the shaded area shown in the chart. Use the indicated restrictor
position.

5' (min.)

(1.5 M)

0 feet

11' (max)

(3.4 M)

5 feet

(1.5

M)

0 feet

5 feet

(1.5

M)

12'(max)

(3.7 M)

0 feet

0 feet

NOTE:
Horizontal sections require a 1/4" (6 mm) rise every 12" (300 mm) of travel.

12'(max)

(3.7 M)

NOTE:
Restrictor positions
are based upon lab
tests. The ideal
restrictor position may
vary slightly,
especially when the
termination is near a
demarkation line.

Restrictor

Position # 5

NOTE:
A minimum 2' (.5 M) rise is
required directly off of the stove.

NOTE:
A minimum 1' (.3 M)
horizontal run is required.

Restrictor

Position # 1

5' (min.)
(1.5 M)

11' (max)
(3.4 M)