Approved Venting Configurations for Vertical Terminations with Two 90
°
Elbows
• The termination must fall within the shaded area shown in the chart. Use the indicated restrictor position.
NOTE:
Horizontal sections require a 1/4" (6 mm)
rise every 12" (300 mm) of travel.
Restrictor
Position # 7
Restrictor
Position #6
NOTE:
Restrictor positions are
based upon lab tests.
The ideal restrictor
position may vary
slightly, especially when
the termination is near a
demarkation line.
11 feet (min.)
Restrictor
Position # 5
Restrictor
Position # 4
NOTE:
A min. 8' (2.4 M) of vertical
vent must be used.
NOTE:
The vent
must
terminate
within one
of the
shaded
regions.
0 feet
5 feet
(1.5 M)
10 feet
(3 M)
0 feet
0 feet
0 feet
16'(max)
(4.9 M)
8 feet (min.)
(2.4 M)
5 feet
(1.5 M)
10 feet
(3 M)
15 feet
(4.6 M)
20 feet
(6 M)
25 feet
(7.5 M)
30 feet
(9.1 M)
35' (max)
(10.7 M)
5 feet
(1.5 M)
10 feet
(3 M)
15 feet
(4.6 M)
20 feet
(6 M)
25 feet
(7.5 M)
30 feet
(9.1 M)
35' (max)
(10.7 M)
8 feet (min.)
(2.4 M)
5 feet
(1.5 M)
10 feet
(3 M)
16'(max)
(4.9 M)