Installation – Avalon Firestyles 564 SS Gas Installation User Manual
Page 27

Installation
(for qualified installers only)
2 7
© Travis Industries
4 0 7 0 6 2 0
100-01188_000
Rear Vent Configuration with Horizontal Termination (no vertical rise)
•
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and
diffuser positions.
Optional 45° Elbow
Termination
See the charts below to
determine maximum vent
3 feet
0 feet
0 feet
4' (max)
• Exhaust Restrictor # 0 (stock)
• Intake Restrictor # 1 (stock)
• Diffuser Position # 1 (stock)
Vent with No 45° Elbow
3 feet
0 feet
0 feet
2' (max)
Vent with 1 45° Elbow
• Min. 4" Horizontal Section
• Max. 24" Horizontal Section(s)
• Min. 4" Horizontal Section
• Max.48" Horizontal Section(s)
• Exhaust Restrictor # 0 (stock)
• Intake Restrictor # 1 (stock)
• Diffuser Position # 1 (stock)