Fireplace Placement Requirements
•
The fireplace requires a 1/2" clearance from the angled sides and back of the fireplace to the framing
members. No material (insulation, framing, etc.) may be placed into this area.
•
Fireplace must be installed on a level surface capable of supporting the fireplace and vent
•
Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)
•
This heater may be placed in a bedroom. Please be aware of the large amount of heat this appliance
produces when determining a location.
Clearances
•
When installed, walls in front of the fireplace must be a minimum 1" to the side of the fireplace.
•
Due to the high temperature, the heater should be located out of traffic and away from furniture and
draperies.
•
Fireplace must be placed so the vents below and above the glass do not become blocked.
Raised Fireplaces
•
The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace
(155 Lbs.) and vent.