Supply air temperature sensor – Auto-Zone Control Systems Auto-Zone CV & CV-EX Systems Installation & Operation (Version 01C) User Manual
Page 26

Section 2
Auto-Zone CV & CV-EX
2-14
Installation and Wiring
Supply Air Temperature Sensor
The Supply Air Temperature Sensor should be located as close to the rooftop unit
discharge as possible for the best response. Locate the sensor in the center of the widest
part of the duct. Use the supplied template and a 5/16" drill to make a hole for the sensor.
Install the gasket over the probe and mount securely to the duct using the supplied sheet
metal screws. Be sure the gasket is compressed to provide an air-tight seal. For best
accuracy, apply insulation on the outside of the duct, over the sensor. This will help
prevent thermal gradients from affecting the sensor.
Figure 2-10:
Supply Air Temperature Sensor Installation
Mounting Plate
Gasket
Adhesive Backed Drill Guide
Mounting Template
11-1/2" (OE231)
5-1/2" (OE230)
Mounting Plate
4.0"
3/4"
1/4" Hex Head Sheet Metal Screws
Thread
Together
Duct Work
Drill 5/16" Hole In Ductwork For Probe
Leads Are Non-polarized.
Butt Splice Leads To 24 Gauge
Wire Minimum. Connect Leads
To "Analog In" And "Ground"
At Controller.