Checking the minilink network loop – cv-ex, Diagram meter set to read dc volts, Overview – Auto-Zone Control Systems Auto-Zone CV & CV-EX Systems Installation & Operation (Version 01C) User Manual
Page 104: Measurements, Action

Section 4
Auto-Zone CV & CV-EX
4-26
Start-Up and Troubleshooting
Checking the MiniLink Network Loop – CV-EX
Diagram
Meter Set To Read DC Volts
+
-
+
-
+ . VDC
to
+4.0 VDC
R - to - G
T - to - G
+
-
+
-
To Other MiniLinks
Or CommLink
On The Network Loop
To Other MiniLinks
Or CommLink
On The Network Loop
MiniLink
MiniLink
To CV Controllers
And System Manager
On Local Loop
To CV Controllers
And System Manager
On Local Loop
2 0
+ . VDC
to
+4.0 VDC
2 0
The indicated readings are typical of a normally operating system. Actual readings may
vary slightly due to the number of units installed and other factors. Any significant
deviation from these values generally indicates a problem.
Note: These tests assume that the CommLink is connected and powered, and that all
MiniLinks, which are connected, are also powered.
Overview
Proper loop voltages are essential for reliable communications. It is normal to see fluctua-
tions on an operating communications loop. The average value should be close to the
acceptable range described below. Values will vary upon initial powerup for about 15-30
seconds as normal communications occur.
Measurements
Local Loop
Acceptable Range
T - G (SHLD)
2.0 - 4.0 Volts DC
R - G (SHLD)
2.0 - 4.0 Volts DC
Action
Condition Action
Readings near Zero Volts.
Check for shorted wiring.
If voltages are too high or too
low on either side.
1. One or more devices connected to this loop may
have damaged comm driver chips. Replace the
driver chip. See Figure 4-10 & 4-11.
2. Wiring errors. Check for multiple loops inadver-
tently “cross connected”, short circuits, etc.