Checking commlink driver – cv, Diagram, Overview – Auto-Zone Control Systems Auto-Zone CV & CV-EX Systems Installation & Operation (Version 01C) User Manual
Page 100: Measurements, Action, Local loop acceptable range, Condition action

Section 4
Auto-Zone CV & CV-EX
4-22
Start-Up and Troubleshooting
Checking CommLink Driver – CV
Diagram
Set Your Meter
To Read DC Volts
+
-
+
-
+
-
T-To-G
+3.1 VDC
To
+3.2 VDC
R-To-G
+3.4 VDC
To
+3.6 VDC
Communications
Loop
Disconnected
CommLink IV
To 24 VAC
Power Supply
MODEM
RS-232
Serial #
COMPUTER
USB
10/100
ETHERNET
DIAG
24
V
T
T
G
G
R
R
GN
D
485 LOOP
485 LOOP
POWER
ACT
LNK
USB
C
onf
ig
No
rm
al
The CommLink IV Must Be
Powered Up For These Tests
Overview
This test checks for proper Communications Loop voltages coming from the CommLink IV.
Tip: The Loop LED (located on the front panel) should “flicker” when the CommLink IV
is attempting to communicate. The Loop LED will flicker more noticeably for a
few seconds when first powered up. If the LED does not flicker, the unit is not
functioning.
Proper loop voltages are essential for reliable communications. It is normal to see fluctua-
tions at this point on the CommLink IV. The average value should be close to the accept-
able range described below. Values will vary upon initial powerup for about 10-15 sec-
onds as the unit attempts to communicate.
Measurements
Local Loop
Acceptable Range
T - G (SHLD)
3.1 - 3.2 Volts DC
R - G (SHLD)
3.4 - 3.6 Volts DC
Action
Condition Action
If voltages are too high or
too low on either side.
1. The CommLink IV has a damaged comm driver chip.
Replace the CommLink IV. The driver chip is not
field-replaceable.