Page 40

background image

Elgar CW-M Series

4-8

M161570-01

4.4 SETTING THE PHASE ANGLE

For multiphase operation, set switches 9 through 12 for the desired phase
angle as specified below, in Table 4

–2.

Table 4

–2. Phase Angles

Leading Phase Angle

Switch 9

Switch 10

Switch 11

Switch 12

0

ON

ON

ON

ON

30

ON

OFF

ON

ON

45

OFF

ON

ON

ON

60

OFF

OFF

ON

ON

90

ON

ON

ON

OFF

120

ON

OFF

ON

OFF

135

OFF

ON

ON

OFF

150

OFF

OFF

ON

OFF

180

ON

ON

OFF

ON

210

ON

OFF

OFF

ON

225

OFF

ON

OFF

ON

240

OFF

OFF

OFF

ON

270

ON

ON

OFF

OFF

300

ON

OFF

OFF

OFF

315

OFF

ON

OFF

OFF

330

OFF

OFF

OFF

OFF

The CW-M Series front panel display for B Phase and C Phase units will
display the leading phase angle in degrees that the DIP switches have
been set for. For a typical 3 phase set-up, the CW-M Units and phase
angle relationships are:

The A Phase at 0°, or reference phase. Switches 9 through 12 should be
ON for the A Phase Master CW-M Unit to set 0°.

The B Phase is set for a +240° or 240° leading phase angle (same as a -
120° or 120° lagging phase angle) relative to A Phase at 0° Reference.
This would have Switch 9 OFF, Switch 10 OFF, Switch 11 OFF, and
switch 12 ON.

The C Phase is set for a +120° or 120° leading phase angle (same as a -
240° or 240° lagging phase angle) relative to A Phase at 0° Reference.
This would have Switch 9 ON, Switch 10 OFF, Switch 11 ON, and switch
12 OFF.

In this fashion, the phase rotation/sequence will be A-B-C-A-B-C etc.