Elgar CW-M Series

M161570-01

3-15

To utilize remote sensing at the user's load, follow these steps:

1. Remove the protective cover from the terminal block.

2. Route the cables through the strain relief device located above the terminal

block. Twisted shielded leads for power and sense leads are recommended
for the lowest noise operation. If used, shields should be connected to a CW
output terminal block GND ground connector, as shown in Figure 3-9.

3. Disconnect local

–sense shorting jumpers. See Figure 3-9.

4. Connect the sense leads as shown in Figure 3-9.

5. Reinstall the protective cover on the terminal block.

Figure 3-9. Sense Connections