2. The paging terminal and transmitters must be alphanumeric message capable.

3. The paging terminal must be P.E.T. (Paging Entry Terminal) protocol capable. P.E.T. is the

protocol utilized by message entry devices such as the Motorola Alphamate when directly connected
to the paging terminal.

4. There must be a direct connect serial port available on the paging terminal for a direct connection of

the unit or an alphanumeric modem port available for dial in access to the terminal.

5. The maximum distance (length of the RS-232 cable) between the paging terminal and the API-8/232

is 50 feet (15.2m) for a direct connection (without the use of short-haul modems etc.)

API-8/232 Specifications
Enclosure

22 Gauge Steel / Black Powder Coat Finish (If supplied)

Dimensions (L x W x H)

10” x 4.5” x 2” (In Enclosure)

Weight: 2.44

lbs

(In

Enclosure)

Power Supply:

50 Watts,110 VAC 50/60Hz
12-18VAC (20VAC Max.)or 18-24VDC @ 400mA Maximum (30
VDC Max.)

Operating Temperature:

0 to 70 Degrees Celsius

Storage Temperature:

-40 to 125 Degrees Celsius

Programming Software:

Pager Interface Programming Software (Vers. 2.0 for WIN 95/NT)

Programming Cable:

RS232 (DB9-Male to DB9-Female)

Direct Connect Paging Protocol:

TAP, PET

Direct Connect Paging Baud Rate:

1200

Direct Connect Paging Settings:

E, 7,1

Direct Connect Paging Port:

DB9 Female

Paging

Retries: Programmable

1-99

Trouble Conditions:

Loss of primary power, telephone line interruption and paging
system communication failure. Indication via on board piezo,
&flashing LED. Auxiliary trouble output contacts programmable
for ON, OFF, or PULSE operation.

Trouble Silence Contacts:

Normally open input contacts, momentary closure will silence

trouble
System Reset Contacts:

On board, Normally Open. Momentary Closure resets board


API-8/232 Contact Input Specifications

Contact Inputs:

8 Optically Isolated

Dry Contact or Wetted Voltage (Select Via On-Board Jumpers)

Wetted

Voltage

(0-48V)

Message Size:

Max. 80 Characters /condition/input

Input Type:

Normally Open or Normally Closed

Escalation:

Alarm

Condition

Re-paged if not reset/acknowledged within time

limit (programmable 1- 60 minutes)

Repetition:

Alarm Message can be re-paged two or three times consecutively

(Programmable)

PAGE 2-2


API-8/232 RS232 Input Port Specifications