PROFIBUS DP Slave Communication Module DVPPF02-H2

DVP-PLC Application Manual

10

of the master. When DVPPF02-H2 is used as PROFIBUS DP slave, you have to add the GSD file of

DVPPF02-H2 into the configuration tool of PROFIBUS DP master. The GSD file of DVPPF02-H2 is available

for download at Delta’s website http://www.delta.com.tw/.

6

LED Indicators & Trouble-shooting

There are two LED indicators on DVPPF02-H2, POWER LED and NET LED. POWER LED displays

whether the power supply of DVPPF02-H2 is normal. NET LED displays whether the communication of

DVPPF02-H2 is connected normally.

ƒ POWER LED

LED status

Indication

How to correct

Green light steady on

The power is normal.

--

Off

No power

1. Check if the power of DVP-EH2 is normal.

2. Check if the connection between

DVPPF02-H2 and DVP-EH2 is normal.

ƒ NET LED

LED status

Indication

How to correct

Off No

power

1. Check if the power of DVP-EH2 is normal.

2. Check if the connection between

DVPPF02-H2 and DVP-EH2 is normal.

Red light steady on

DVPPF02-H2 is operating but
is not connected to
PROFIBUS DP network.

Check if DVPPF02-H2 is normally connected to
PROFIBUS DP bus.

Red light flashes

Depending on the value in
CR#251

See the error code table below for how to
correct.

Green light steady on

DVPPF02-H2 is in data
exchange status

--

ƒ Error codes

Code

Description

How to correct

00

DVPPF02-H2 operates normally.

--

01 Hardware

error

Send your DVPPF02-H2 back to the manufacturer for
repair.

02

PROFIBUS DP watch dog error

Check if DVPPF02-H2 is normally connected to
PROFIBUS DP bus.

03

Address setting error (0, or exceeding
0x01 ~ 0x7D)

Set the address of DVPPF02-H2 to be within the range
0x01 ~ 0x7D and re-power DVP-EH2.

04

24V low voltage error

Check if the power supply voltage of DVP-EH2 is
normal, and check if DVPPF02-H2 is normally
connected to DVP-EH2.

05

5V low voltage error

Send your DVPPF02-H2 back to the manufacturer for
repair.

7

Application Example I

¡ Target

Complete data exchange between S7-300 (Siemens PLC) and DVP-EH2 (Delta PLC) through PROFIBUS

DP network.