3.2.- INSTALLATION

The unit is installed on a DIN rail.

All active conductors that supply the loads or the part of the installation where the earth leak-

age protection with this unit is required must pass through the sensor associated with the unit.

The unit must be mounted inside an electric panel.

Likewise, it must be connected to a fuse-protected power circuit, in accordance with its power

supply range and consumption. In turn, the power circuit must be fitted with a circuit breaker

switch or an equivalent device, in order to be able to disconnect the unit from the power supply

mains.

Note: The connection diagram suggests a cable section of 1- 1.5 mm.

Recommended torque 0.5-0.6 Nm.

Terminals, opening covers or removing elements can expose parts that are haz-

ardous to the touch while the unit is powered

3.3.- UNIT TERMINALS

Table 2: Unit terminals�

Unit terminals

1, 2 : External current sensor input.

8: External Test/Reset input with button.

3, 6, 10, 12: Not used

9, 11: Auxiliary Power Supply

4: Prealarm/Fault relay output: NO Contact

13: Trip relay output: NO Contact

5: Prealarm/Fault relay output: COM Contact

14: Trip relay output: NC Contact

7: External Test/Reset input with button.

15: Trip relay output: COM Contact

Figure 1:Unit terminals�

8

RGU-2 Earth Leakage Relay

Instruction Manual