When the instantaneous leakage current has been measured, the

RGU-2 unit will operate in

accordance with the programmed parameters:

- Trip current (

IΔn)

- Trip delay time (

td)

As a result, the status of the device's output contacts will be changed. The output of this contact

will be used as follows, depending on the final application type:

- Earth leakage protection (IEC61008-1), the circuit breakers are activated.

- Earth leakage monitoring (IEC62020), alarm alerts, sound and/or visual devices.

5.1.- KEYBOARD FUNCTIONS

The unit has 3 keys:

RESET, TEST and PROG.

PROG Key

Pressing this key displays the different screens and opens the programming mode (hold down

the key for 2 seconds) to adjust the different programming parameters.

This key is sealable; it is supplied with a small hole where the configuration can be physically

disabled.

TEST Key

Press the

TEST key to check the connection status of the sensor element and force the tripping

of the unit.

RESET key

Locally rearms the electronic relay, resetting the status of the output contacts to the normal

standby status.

If the unit is in standby status, it will scroll down the model and version (5s) on the green

LCD.

5.2.- DISPLAY

The unit has a green/red backlit LCD. The background will be green under normal conditions.

The display will be red in case of events that cause an action (protection trigger or circuit

breaker being tripped).

Figure 8:Display