1�- VERIFICATION UPON RECEPTION
Check the following points when you receive the unit:
a) The unit meets the specifications described in your order.
b) The unit has not suffered any damage during transport.
c) Perform an external visual inspection of the unit prior to switching it on.
d) Check that it has been delivered with the following:
- a seal to lock the programming button.
- installation guide.
If any problem is noticed upon reception, immediately contact the transport
company and/or
CIRCUTOR's after-sales service.
2�- PRODUCT DESCRIPTION
RGU-2 is a protection and/or measurement relay (MRCD/RCM). It is a smart earth leakage
protection system composed of the following elements:
- A detecting element or sensor,
- A relay,
- A circuit breaker,
The unit is fully programmable. It is supplied with the following:
-
3 Keys, used to TEST/RESET and program the unit.
-
2 operation LEDs that display the unit's status.
-
LCD Display that displays messages and operation values.
-
An LED Bar that displays qualitative level of leakage information.
-
Plug-in terminal strips.
The unit is characterised by its reduced dimensions (2 modules mounted on a DIN rail).
It has been designed for single-phase, three-phase or three-phase with neutral low voltage
electrical installations. It is suitable for all neutral rates (VT, TN, IT), either as the main protection
element (MRCD) or for complementary purposes (RCM).
In the case of VT/TN-S systems, it can be used as a MRCD (IEC 60947-2) or a RCM (IEC
62020). It can only be installed as an RCM in other systems.