beautypg.com

CIRCUTOR RGU2 Series User Manual

Page 15

background image

5.5.- OUTPUTS

The unit has two independent output relays:

5�5�1� TRIP RELAY, TRIP

Switched contact relay (terminals 13, 14 and 15 in

Figure 1

)

The unit can be programmed to modify the logical status of the contact (

refer to section 5.6.3)

from the standard NC/NO status to the NO/NC positive safety status.

The positive safety status is shown on all screens that refer to the

TRIP, with the + sign (

Figure

14

). The prealarm/fault screen will not be affected by this.

Figure 14: Positive safety status screen

5�5�2� AUXILIARY RELAY, AUX

Simple contact relay (terminals 4 and 5, and

Figure 1) non-interlocking. Its operation can be

programmed as a prealarm or fault relay (

refer to section 5.6.2 )

Prealarm (ALAR), activated when the > 0.5•IΔn, in 200 milliseconds. The logical sta-

tus of the contact (

refer to section 5.6.3) can be changed from the NO standard status to the

NC positive safety status.

The Fault relay (AUXF), is a

ctivated to notify fault events in the unit, such as:

undervoltages (the voltage is below the unit's operation voltage - the unit turns off below this

voltage) or faults in the external sensor.

In this case, the relay operates with the positive safety status.

Positive safety is shown with the + sign (only in the screens that refer to the AUX relay).

Figure 15:Screens with a positive safety status�

15

Instruction Manual

RGU-2 Earth Leakage Relay