Page 10

background image

3�4�2� AS A MONITOR (RCM)

Figure 4:Connection diagram of the unit as a monitor�

4�- START-UP

4.1.- DEFAULT CONFIGURATION

When the unit is powered with auxiliary voltage, the

ON LED is lit green and the LCD is backlit

green.

The name of the model, firmware version and a fixed screen that shows the conditions in which

the earth leakage protection is characterised will be displayed.

This screen is displayed by default when there are no external actions (

Figure 5

).

Figure 5: Earth leakage protection screen

The unit is supplied with the following default factory configuration:

-

Trip current scale (IΔn) : 30mA

- Trip time scale (

td) :Instantaneous curve (IN)

- Frequency: 50 Hz

- Auxiliary relay function: Fault relay

- Polarity of the trip relay: Standard

- Polarity of the auxiliary relay: Standard

10

RGU-2 Earth Leakage Relay

Instruction Manual