beautypg.com

Technical features – CIRCUTOR RGU2 Series User Manual

Page 23

background image

6�- TECHNICAL FEATURES

Power Supply

Voltage

110V AC o 230V AC

Tolerance

-20%, +20%

Frequency

50 Hz - 60 Hz

Maximun consumption

6 VA ( 110V AC) - 6 VA ( 230V AC)

Voltage pulse

4KV

Installation category

CAT III 300V

Current measurement circuit

Sensor input

Transformer type TP-WG, WG o WGC to 500/1

Measurement system

short circuit

Frequency

50Hz -60Hz

Accuracy in measurement

Accuracy current measurement

< 10%

Characteristics of trip relay TRIP

Maximum voltage open contacts

1000V AC

Isolation voltage

2500V AC

Thermal current, Ith

10A

Maximum switching power

2500 VA

Electrical life ( 3A)

30*10

3

Characteristics of auxiliar relay AUX

Maximum voltage open contacts

1000V AC

Isolation voltage

2000V AC

Thermal current, Ith

5A

Maximum switching power

1250 VA, 150W

Electrical life ( 3A)

10

5

Environmental characteristics

Work temperature

-10ºC ... +50ºC

Storage temperature

-25ºC ... 70ºC

Humidity (without condensation)

5 ... 95%

Maximum altitude

2000 m

Pollution resistance

Category 2

Protection degree

IP40

Mechanical caracteristics

Dimensions

35x112x84 mm

Weight

150gr

Housing

Polycarbonate V0

Standards

Low-voltage switchgear and controlgear � Part 2:

Circuit-breakers

IEC 60947-2 Anexo M: 2011

Electrical accessories - Residual current monitors for

household and similar uses (RCMs)

IEC 62020: 1998

23

Instruction Manual

RGU-2 Earth Leakage Relay