Technical features – CIRCUTOR RGU2 Series User Manual
Page 23

6�- TECHNICAL FEATURES
Power Supply
Voltage
110V AC o 230V AC
Tolerance
-20%, +20%
Frequency
50 Hz - 60 Hz
Maximun consumption
6 VA ( 110V AC) - 6 VA ( 230V AC)
Voltage pulse
4KV
Installation category
CAT III 300V
Current measurement circuit
Sensor input
Transformer type TP-WG, WG o WGC to 500/1
Measurement system
short circuit
Frequency
50Hz -60Hz
Accuracy in measurement
Accuracy current measurement
< 10%
Characteristics of trip relay TRIP
Maximum voltage open contacts
1000V AC
Isolation voltage
2500V AC
Thermal current, Ith
10A
Maximum switching power
2500 VA
Electrical life ( 3A)
30*10
3
Characteristics of auxiliar relay AUX
Maximum voltage open contacts
1000V AC
Isolation voltage
2000V AC
Thermal current, Ith
5A
Maximum switching power
1250 VA, 150W
Electrical life ( 3A)
10
5
Environmental characteristics
Work temperature
-10ºC ... +50ºC
Storage temperature
-25ºC ... 70ºC
Humidity (without condensation)
5 ... 95%
Maximum altitude
2000 m
Pollution resistance
Category 2
Protection degree
IP40
Mechanical caracteristics
Dimensions
35x112x84 mm
Weight
150gr
Housing
Polycarbonate V0
Standards
Low-voltage switchgear and controlgear � Part 2:
Circuit-breakers
IEC 60947-2 Anexo M: 2011
Electrical accessories - Residual current monitors for
household and similar uses (RCMs)
IEC 62020: 1998
23
Instruction Manual