5�6�1 trip current i, And trip delay time t, D ����������������������������������������������16 – CIRCUTOR RGU2 Series User Manual

Page 16

background image

PROG

Trip delay time, t

d

The current value will start flashing. Press the

RESET key gradually to

browse all programming values (

Tabla 3

).

Accept with the

PROG key.

PROG

Trip current, t

d

The current value will start flashing. Press the

RESET key gradually to

browse all programming values (

Tabla 3

).

Accept with the

PROG key.

If changes have been applied, SAVE will be displayed for 3 sec-

onds and the unit will exit the programming screens.

If changes have not been applied, EXIT will be displayed for 3 sec-

onds and the unit will exit the programming screens.

PROG

Note: If you reach the last value of the Trip current to be configured and you do not press the

PROG key to accept the changes, the unit will exit the programming screen after 5 seconds

and the changes will not be saved.

Table 3:Relationship of Currents and Trip Times to be programmed�

Trip current IΔn

Trip time td

30mA

IN ( Instantaneous )

(1)

0.1A

SE (Selective)

(1)

0.3A

0.1s

0.5A

0.2s

1A

0.3s

2A

0.5s

3A

0.8s

5A

1s
2s
3s
5s

(1)

The trip curves are shown in Appendix A

5.6.- PROGRAMMING

5�6�1 TRIP CURRENT I

Δ

n

and TRIP DELAY TIME t

d

The earth leakage protection screen must be displayed to program the current and delay time

of the trip. Hold down the

PROG key for 2 seconds.

16

RGU-2 Earth Leakage Relay

Instruction Manual