5�6�1 trip current i, And trip delay time t, D ����������������������������������������������16 – CIRCUTOR RGU2 Series User Manual
Page 16

PROG
Trip delay time, t
d
The current value will start flashing. Press the
RESET key gradually to
browse all programming values (
Accept with the
PROG key.
PROG
Trip current, t
d
The current value will start flashing. Press the
RESET key gradually to
browse all programming values (
Accept with the
PROG key.
If changes have been applied, SAVE will be displayed for 3 sec-
onds and the unit will exit the programming screens.
If changes have not been applied, EXIT will be displayed for 3 sec-
onds and the unit will exit the programming screens.
PROG
Note: If you reach the last value of the Trip current to be configured and you do not press the
PROG key to accept the changes, the unit will exit the programming screen after 5 seconds
and the changes will not be saved.
Table 3:Relationship of Currents and Trip Times to be programmed�
Trip current IΔn
Trip time td
30mA
IN ( Instantaneous )
(1)
0.1A
SE (Selective)
(1)
0.3A
0.1s
0.5A
0.2s
1A
0.3s
2A
0.5s
3A
0.8s
5A
1s
2s
3s
5s
(1)
The trip curves are shown in Appendix A
5.6.- PROGRAMMING
5�6�1 TRIP CURRENT I
Δ
n
and TRIP DELAY TIME t
d
The earth leakage protection screen must be displayed to program the current and delay time
of the trip. Hold down the
PROG key for 2 seconds.
16
RGU-2 Earth Leakage Relay
Instruction Manual