5�6�3 FREQUENCY AND STATUS OF THE OUTPUT RELAY CONTACTS
To program the frequency and status of the output relay contacts,
TRIP and AUX, open the
instantaneous current screen and hold down the
PROG key for 2 seconds.
PROG
PROG
PROG
PROG
RESET
RESET
RESET
RESET
RESET
RESET
RESET
Frequency (50Hz by default)
Select the frequency: 50Hz or 60Hz.
Accept with the
PROG key.
Status of the TRIP relay contact
(
STD, by default)
STD: Standard NC/NO status
POS: NO/NC positive safety status
When this option is activated, the
+ sign
will appear on all screens that refer to the
TRIP relay.
Accept with the
PROG key.
Status of the AUX relay contact
(
STD, by default)
STD: Standard NO status.
POS: NC positive safety status.
When this option is activated, the
+ sign
will appear on all screens that refer to the
AUX relay.
Accept with the
PROG key.
If changes have been applied, SAVE will be displayed for 3 seconds
and the unit will exit the programming screens.
If changes have not been applied or the keyboard has been inactive
during 5 seconds,
EXIT will be displayed for 3 seconds and the unit will
exit the programming screens.