- input signal
0...0.005...1.2I
n
; 0.05...1.2U
n
for
current, voltage
0...0.1...1.2I
n
; 0...0.1...1.2U
n
; for
coefficients Pf
i
, t
j
i
,
j
frequency
45...66...100 Hz;
sinusoidal (THD
8%)
- power factor
-1...0...1
- ambient temperature -25...23...+55°C
- storage temperature
-30...+70°C
- relative air humidity
25...95% (
inadmissible condensation
)
- admissible peak factor of:
- current
2
- voltage
2
- external magnetic field
0...400 A/m
- short duration overload (5 s):
- voltage inputs
2Un (max.1000 V)
- current inputs
10 In
- work position
any
- minimal distance between meters 1.5 cm
- power consumption:
- supply circuit < 6 VA
- in voltage/current circuit < 0.05 VA.
- input power
6 VA
Additional Errors in % of the basic error:
- from frequency of input signals
< 50%
- from ambient temperature changes
< 50%/10°C
Standards Fulfilled by the Meter:
Electromagnetic Compatybility:
- noise immunity acc.to EN 61000-6-2
- noise emissions acc. to EN 61000-6-4
Safety Requirements: acc. to EN 61010-1 standard
l
isolation between circuits: basic,
l
installation category III,
l
pollution level 2,
l
maximal earth-to-phase voltage 600 V
l
altitude above sea level < 2000 m,
Preheating Time
15 minutes