CIRCUTOR DHB Series User Manual
Page 45

45
7076
7538
tG_max
r
Maximal value of reactive/active
power ratio
7078
7539
FI_min
r
°
Minimal value of phase shift
7080
7540
FI_max
r
°
Maximal value of phase shift
7082
7541
FrEq_min
r
Hz
Minimal value of frequency
7084
7542
FrEq_max
r
Hz
Maximal value of frequency
7086
7543
PAv_min
r
Minimal value of mean active power
7088
7544
PAv_max
r
Maximal value of mean active power
W
W
7090
7545
UAv_min
r
Minimal value of 10 minutes’ mean
voltage
7092
7546
UAv_max
r
Maximal value of 10 minutes’ mean
voltage
V
V
7094
7547
FAv_min
r
Minimal value of 10 seconds’ mean
frequency
7096
7548
FAv_max
r
Maximal value of 10 seconds’ mean
frequency
Hz
Hz
7098
7549
EP_PoS1
r
Active energy input (the counter of
turning the register 7550 is reset every
9999999.9 kWh)
7100
7550
EP_PoS2
r
Active energy input
(modulo 100000.0)
100MWh
kWh
7102
7551
EP_nEG1
r
Active energy output (the counter of
turning the register 7552 is reset every
9999999.9 kWh)
7104
7552
EP_nEG2
r
Active energy output (modulo
100000.0)
100MWh
kWh
7106
7553
Eq_PoS1
o
Reactive energy input (the counter of
turning the register 7554 is reset every
9999999.9 kVarh)
7108
7554
Eq_PoS2
o
Reactive energy input (modulo
100000.0)
100Mvarh
kvarh
7110
7555
Eq_nEG1
o
Reactive energy output (turning counter
of the register 7556 is reset every
9999999.9 kVarh)
7112
7556
Eq_nEG2
o
Reactive energy output (modulo
100000.0)
100Mvarh
kvarh