CIRCUTOR DHB Series User Manual
Page 21

21
LEd_1
LEd_2
LEd_3
LEd_4
Supporting of alarm signaling. In the
situation when the support function is
switched on after
the alarm state retreat, the signal-
ing diode is not put out. It signals
the alarm state till the moment of its
extinction by means of the
button combination.
The function concerns only and ex-
clusively the alarm signaling, that is
the relay contacts will operate without
support in compliance with the cho-
sen alarm type.
on – support switched on
oFF – support switched off
P_An
Kind of input value type, which the
analog output has to react on.
U – RMS voltage
I – RMS current
P – active power
q – reactive power
S – apparent power
PF – active power factor
tG – ratio of reactive power to active
power
FI – phase shift
FrEq - frequency
EPPoS – active energy input
EPnEG – active energy output
EqPoS – reactive energy input
EqnEG – reactive energy output
PAv – mean active power
UAv – 10 minutes’ mean voltage
FAv – 10 seconds’ mean frequency.
An_Lo
Lower threshold of the analog output.
One must give the value for which
we want to obtain 0 on the analog
output.
-19999M ... 99999M
An_HI
Upper threshold of the analog output.
One must give the value for which we
want to obtain the maximal signal on
the analog output (20 mA or 10V).
-19999M ... 99999M
tYPA
Type of the analog output
0_10U – voltage 0...10 V
0_20A – current 0...20 mA
4_20A – current 4...20 mA