Technical data, Measuring ranges table 8 relay outputs, Voltage programmable 0 v load resistance ³ 500 w – CIRCUTOR DHB Series User Manual
Page 48: Galvanically isolated, Resolution 0.01% of the range

48
Measured value
Indication range
Measuring range
Basic error
Current 1 A
0.000...12 kA
0.005...1.200 A~
±0.2%
5 A
0.000... 60 kA
0.025...6.000 A~
Voltage L-N
100 V
0.0...0.48 MV
0.5...120 V
±0.2%
400 V 0.0 ...1.92 MV 2.0...480 V
Frequency
45.00...100.00 Hz
45.0...66.0...100 Hz
±0.2%
Active power
-19999... 99999 MW
-2.88 kW...1.40 W...2.88 kW
±0.5%
Reactive power
-19999 Mvar...0.00
...99999 Mvar
-2.88 kvar...1.40 var...2.88 kvar
±0.5%
Apparent power
0.00...99999 MVA
1.40 VA... 2.88 kVA
±0.5%
Coefficient PF
-1...0...1
-1...0...1
±0.5%
Tangens
j
i
-1.2...0...1.2 -1.2...0...1.2 ±1%
j
0...359
0...359 ±1%
Active energy
0...9 999 999.9 kWh
0...9 999 999.9 kWh
±0.5%
Reactive energy
0...9 999 999.9 kvarh
0...9 999 999.9 kvarh
±0.5%
Current time
0.00...23.59
0.00...23.59
1 second
/24 h
Ku – voltage transformer ratio: 0.1...4000.0
Ki – current transformer ratio: 1...10000
8. TECHNICAL DATA
Measuring Ranges
Table 8
Relay outputs
l
relays, voltageless NOC contacts
load-carrying capacity 250 V/0.5 A
l
relays, voltageless switched contacts
load-carrying capacity 250 V/0.5 A
(DHB-324)
Analog output (DHB-324)
l
current programmable 0/4...20 mA
load resistance
500 W
l
voltage programmable 0...10 V
load resistance
³ 500 W
l
galvanically isolated
l
resolution 0.01% of the range