Electrical features – CIRCUTOR CIReQ User Manual
Page 9
_______________________________________________________
_________________________________________________________________________________________________________
CIR-eQ User’s Manual
9 of 36
POWER LED
is on when the unit is powered. It is off when the unit is not powered.
The START/STOP
is used to start or stop the recording of quality events of the network.
Hold the button during
3 seconds.
(*) The REC LED
has three basic modes. When it is off, the unit is not recording
information. When it is permanently on, the unit is recording electrical parameters, which
are stored in the SD memory card. When the REC LED is flashing, there is an error in
the SD memory card. The REC LED can be flashing for the following reasons:
•
No memory card inserted in the unit's SD card slot.
•
The memory card inserted does not have the correct format or data can not be
written. (for example, if the card is writen protected or it has a FAT32 format; in
that case change the format of the memory card to
FAT16).
(**) The LED L1, L2 or L3 start flashing to indicate that there is an incorrect connection.
The phase LED start flashing when R-S-T sequence is not correct.
CIR-eQ LED’s start flashing to indicate a connection error.
The unit has been installed correctly when the LED’s are permanently on.
4.1.- ELECTRICAL FEATURES
Power supply circuit (connector B, brown and green wires)
AC voltage
100…400 Vac
DC voltage
70…315 Vdc
Frequency
50 or 60 Hz
Consumption 100 / 400 Vac
5,2 / 22 VA
Consumption 70 / 315 Vdc
3 W
Measurement circuit
Voltage
10…400 Vac (ph-neutral)
17…690 Vac (ph-ph)
Frequency
45…65 Hz
Accuracy
Voltage
0,5 % of E.S.
Battery
Devices (until 2011)
NiMH
Devices from 2012 or later
BR2032
Devices manufactured before 2012 has rechargeable battery.
Devices manufactured after 2012, have BR2032 battery. We recommend
replacing it every 5 years.