CIRCUTOR CIReQ User Manual
Page 15

_______________________________________________________
_________________________________________________________________________________________________________
CIR-eQ User’s Manual
15 of 36
Serial number: Enter the 10 digits of the serial number of
CIR-eQ unit used to take the
measurements. The serial number identifies each individual unit. It is written on a
label on the back of the analyzer: “serial no.” starting with 0107XXXXXX.
The serial number is used by the application as the data name (identifier). The setup
file generated by the application will have the xxxxxxxx.xst format, where “xxxxxxxx”
corresponds to the last eight numbers of the unit's serial number.
Report name: You can enter the name of the file for identification purposes. This field is
limited to 16 characters. For example, you can enter the name of the place where the
measurements are going to be taken.
Register period: The registration period is a value that ranges from 1 to 120 minutes (2
hours) and it corresponds to a time interval during which we use to store the average
of the records taken. The analyzer takes 128 samples per cycle of the signals
measured. The registration period indicates the interval desired to take the weighted
mean of all samples taken and it stores this value in the memory. For example, if you
select a registration period of 1 minute, the analyzer calculates the mean of all
samples of the variables registered during that minute and stores the results in the
memory. From that period, the analyzer also stores the maximum and minimum
values measured.