4 log.eva files – CIRCUTOR AR6 Series User Manual
Page 65

AR6 portable network analyzer
User Manual
Page 65 of 69
19.4 LOG.EVA FILES
The AR6 analyzer has a log type called EVA in which the device's events are stored. A
device event is understood as any change of the measurement configuration that
affects the header of STD files, such as switching the unit ON or OFF, modifying the
transformer’s ratios, battery charge status, deleting maximum values or other
parameters. The complete list of events is shown in Table 19-1.
Table 19-1.- Table of variables for LOG.EVA files
Event Name
Description
BAT_OFF
Battery level that causes the unit to switch off.
CLEAR_ENERGY
Deleting energy.
CLEAR_MAX_MIN
Deleting maximum values, minimum values or maximum and
minimum values.
CLEAR_MAX_DEMAND
Deleting maximum demand.
SETUP_CHANGED
Change of a configuration parameter other than transformer’s
ratios
SETUP_TRANS_RATIO
_CHANGED
Change of transformer’s ratio configurations
SETUP_TIME_CHANGED
Change of date and/or time
TRIGGER_ON
Entering in a trip time window (associated with the immediate
subsequent generation
of the REC_START event)
TRIGGER_OFF
Exiting a trip time window (associated with the immediate
subsequent generation
of the REC_STOP event)
DELETED_STD_FILE
Deleting configuration files due to erasing a measurement
POWER_ON
Unit switched on
POWER_OFF
Unit switched off
REC_STOP
Stop manual or trip logging
REC_START
Start manual or trip logging
TRIGGER_CONDITION_ON
Trip activation due to a variable condition
TRIGGER_CONDITION_OFF
Trip deactivation due to a variable condition
EVQ_STOP
Automatic deactivation of events or transients (after detecting 1
EVQ / TRN per second for 15 sec.)
EVQ_START
Automatic enabling of events or transients (after 10 min. has
elapsed since deactivation)