4 current inputs, 5 current clamps, 6 voltage inputs – CIRCUTOR AR6 Series User Manual
Page 14: Current, Inputs, Clamps, Voltage

AR6 portable network analyzer
Page 14 of 69
User Manual
4.4
CURRENT INPUTS
Inputs for current measurement
I1 I2 I3 IN Leakage
Input voltage
0…2 V
RMS
Measurement margin
from 1 to 120% of In
Primary current measurement In
Depends on clamp
Admissible overload
3 In
Consumption
≤0.0004 VA
Accuracy of the instrument
(excluding the clamp)
0.5%
± 1 digit (we must add the margin of error of
the clamp used to this number)
Special features
Earth leakage current measurement via low-
pass filter (option to activate or deactivate)
Input impedance
10 kΩ
4.5
CURRENT CLAMPS
The AR6 can use single-scale or multi-scale clamps. When using single-scale clamps the
instrument automatically recognises the clamps connected to it; in the case of multi-scale
clamps, when the clamps are connected a menu pops up to configure the current transformer’s
ratio (see current clamp configuration).
When using E-FLEX 54 cm multi-scale clamps the scales are as indicated in
Table 4-1.- E-FLEX 54 cm clamps
Clamp
TURNDOWN
RATIO
LED
Range (2.5...100%)
E-FLEX 54 cm (See note 1)
200 A
blue
5…200 A
2,000 A
red
50...2,000 A
20,000 A
blue + red
500...20,000 A
Note 1: E-FLEX clamps have built-in LEDS to indicate the scale at which they are working.
When they work at a low scale the blue LED lights up, when they work at a medium scale the
red LED lights up and when they work at a high scale both LED light up.
4.6
VOLTAGE INPUTS
Inputs for voltage measurement
U1 U2 U3 UN U
EARTH
Input margin
Unom= 10 to 800 V
RMS
phase-neutral
Measured accuracy
0.5%
± 1 digit
Number of inputs
5
Peak voltage
2,500 Vpeak
Bandwidth
3.2 kHz
Input impedance
10 MΩ