5 transients, Peak, Wave – CIRCUTOR AR6 Series User Manual
Page 32: Transients

AR6 portable network analyzer
Page 32 of 69
User Manual
10.2.5 Transients
The detection of transients lets the user detect different types of voltage wave defects. When
the user clicks on the transients menu option the screen in Fig. 10-11 or similar will appear.
Clicking the” Detection mode" window allows the selection among the following options:
Configurable options for detection method:
•
Peak
•
Wave
•
RMS Value
•
Disabled
Fig. 10-9.- Configurable options for capturing transients
PEAK
The detection of transients based on the peak value occurs when the absolute value of one or
several voltage samples exceed a certain threshold value set in this screen. The setting should
be large enough to avoid it from being tripped with normal amplitudes or even those slightly
above 110% of the nominal peak value.
The detection is based on phase-neutral voltage value. If there is no neutral, the set value
should be the maximum phase-phase voltage value divided by
√3
Fig. 10-10.- Peak value defect
Configurable Parameters:
•
Peak voltage in V phase to
neutral
Fig. 10-11.- Configuration for transient detection based on Peak value
WAVE
The detection of transients using the “wave” option occurs when there is a defect in the wave
shape so that the it exceeds the limits of a square defined by a threshold value (V phase to
neutral) and a duration (indicated in % of the period)