Install compact module, 5installation, 2 install compact module – Pilz PSSu K S RS232 Modbus ASCII User Manual

Page 18

background image

5.2

Install compact module

5

Installation

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

5-2

5.2

Install compact module

5200

Install compact module

5-

][Montage Kompaktmodul Trumph

Prerequisite:

The head module must be installed.

If the head module does not have an integrated power supply, a sup-

ply voltage module must be installed to the right of the head module.

A base module with screw terminals may not be installed to the left of

the compact module.

Please note:

All contacts should be protected from contamination.

The mechanics of the compact modules are designed for 50 plug in/

out cycles.

Procedure:

Slot the groove on the compact module on to the mounting rail from

below [1].

Push the compact module back as far as it will go [2].

Make sure that the locking mechanism [3] is pushed downwards, con-

necting the module firmly to the mounting rail.

On the mounting rail, slide the compact module to the left.

NOTICE

Potential contact damage due to twisting!

The contacts for the Module Supply and Periphery Supply can

be bent by twisting the compact modules on the mounting rail.

On the mounting rail, carefully slide the compact module to the

left, in parallel to the adjoining module, until you hear the lateral

mounting hooks on the adjacent module lock into position [4].