beautypg.com

7 operation, 1 messages, Section 7 – Pilz PSSu K S 16DI User Manual

Page 25: Operation, Messages, 7operation

background image

Operation

Operating Manual PSSu K S 16DI
22053­EN­07

25

7

Operation

7.1

Messages

A module error is displayed via the "Err" LED (see section entitled "Display elements"), sig­
nalled to the head module and then entered in the head module's

}

Error stack, with PSSu in system environment A

}

Diagnostic log, with PSSu in system environment B.

The module can detect the following errors:

Error

Explanation

Remedy

Start­up error

Error as the PSSu system starts
up.

Change faulty module.

Configuration error

Incorrect module type configured.

The configured hardware registry
does not match the actual hard­
ware registry.

ST communication error

Error in ST communication with
the head module.

Change faulty module.

Bus termination error

There is no end bracket.

Install a terminating plate with in­
tegrated end angle.

Temperature error: too warm

Temperature in module too high:
Error stack entry

Ensure there is sufficient ventila­
tion in the control cabinet or pre­
vent overload.

Further information on PSSu error messages is available in the online help for the PSSuni­
versal Assistant system software.