7-1
7.1
Messages
7
Operation
7
7000
Operation
Operation
7-
7.1
Messages
7100
Messages
7-
][BA_Betrieb Störung LED "Err" Sys A + B
A module error is displayed via the "Err" LED (see section entitled "Dis-
play elements"), signalled to the head module and then entered in the
head module's
Error stack, with PSSu in system environment A
Diagnostic log, with PSSu in system environment B.
][BA_Betrieb Fehler ST
The module can detect the following errors:
Module error
Explanation
Remedy
Start-up error
Error as the PSSu system starts up.
Change faulty module.
Configuration error
Incorrect module type configured.
The configured hardware registry does
not match the actual hardware regis-
try.
ST communication error
Error in ST communication with the
head module.
Change faulty module.
Bus termination error
There is no end bracket.
Install a terminating plate with inte-
grated end angle.