Technical details
Operating Manual PSSu E F AI U(T)(R)
21993EN05
31
Environmental data
312265
314265
315265
Condensation during op
eration
Not permitted
Shortterm
–
EMC
EN 6100042, EN
6100043, EN 6100044,
EN 6100045, EN
6100046, EN 6100062,
EN 6100064
EN 6100042, EN
6100043, EN 6100044,
EN 6100045, EN
6100046, EN 6100062,
EN 6100064
EN 6100042, EN
6100043, EN 6100044,
EN 6100045, EN
6100046, EN 6100062,
EN 6100064
Vibration
In accordance with the
standard
EN 6006826
EN 6006826
EN 501253
Frequency
10,0 150,0 Hz
10,0 1000,0 Hz
5,0 2000,0 Hz
Amplitude
0,35 mm
0,35 mm
–
Acceleration
1g
5g
0,23 g
Broadband noise
In accordance with the
standard
–
EN 60068264
EN 61373
Frequency
–
5 500 Hz
5 150 Hz
Acceleration
–
1,9grms
0,79 g RMS
Shock stress
In accordance with the
standard
EN 60068227
EN 60068227
EN 501253
Acceleration
15g
15g
2g
Duration
11 ms
11 ms
11 ms
In accordance with the
standard
EN 60068229
EN 60068229
EN 61373
Acceleration
10g
25g
5g
Duration
16 ms
6 ms
30 ms
Supply interruptions
In accordance with the
standard
–
–
EN 50155
Class
–
–
S2, C1, C2
Max. operating height
above sea level
2000 m
5000 m
2000 m
Airgap creepage
In accordance with the
standard
IEC 606641
IEC 606641
EN 501241
Overvoltage category
II
II
OV2
Pollution degree
2
2
PD2
Protection type
In accordance with the
standard
EN 60529
EN 60529
EN 60529
Mounting area (e.g.
control cabinet)
IP54
IP54
IP51
Housing
IP20
IP20
IP20
Terminals
IP 20
IP 20
–