Commissioning

Operating Manual PNOZ m EF 8DI4DO
1002661­EN­02

13

Input circuit

Single­channel

Dual­channel

Example:

E­STOP

without detection of shorts across
contacts

S1

I0

L+

Example:

E­STOP

with detection of shorts across
contacts

I0

T0

S1

S1

T1

I1

T0

I0

Connection examples for the input circuit

Redundant output

K2

L-

O0 (O2)

O1 (O3)

K1

L-

Single output

K3

L-

K4

O0 (O2)

O1 ( O3)

K1

L-

K2

Single output with advanced fault
detection*

K1

L+

L-

K2

O0 (O2)

i0

Connection examples for semiconductor outputs

*Two loads may be connected to each safety output with advanced fault detection, even on
applications in accordance with EN IEC 62061, SIL CL 3. Prerequisite: Feedback loop is
connected, shorts across contacts and external power sources are excluded (e.g. through
separate multicore cables). Please note that, in the event of an error in the feedback loop,
the safety system switches to a safe condition and shuts down all the outputs.