beautypg.com

7 operation, 1 messages, Section 7 – Pilz PNOZ m EF 16DI User Manual

Page 13: Operation, Messages, 7operation

background image

Operation

Operating Manual PNOZ m EF 16DI
1002703­EN­02

13

7

Operation

When the supply voltage is switched on, the PNOZmulti safety system copies the configur­
ation from the chip card.

The LEDs "POWER","DIAG", "FAULT", "IFAULT" and "OFAULT" light up on the base unit.

The PNOZmulti control system is ready for operation when the "POWER" and "RUN" LEDs
on the base unit are lit continuously.

7.1

Messages

Legend:

LED on

LED flashes

LED off

Fault

PO
WE
R

Run Dia

g

Fau
lt

IFa
ult

No supply voltage

Expansion module PNOZ m EF 16DI is running without error

Expansion module PNOZ m EF 16DI is in a STOP condition

Internal error on the expansion module PNOZ m EF 16DI or
on the overall system. Expansion module is in a safe condi­
tion.

External error on the expansion module PNOZ m EF 16DI or
on the overall system. Expansion module is in a safe condi­
tion.

Internal error on the inputs of the expansion module PNOZ m
EF 16DI. Expansion module is in a safe condition, e.g. pulse
error.

External error on the inputs of the expansion module PNOZ m
EF 16DI. Expansion module is in a safe condition.