Controls - upc ddc control (optional) cont – WaterFurnace Versatec Ultra User Manual
Page 39
39
VERSATEC ULTRA SERIES INSTALLATION MANUAL
Status LED (LED3, Green)
Description of Operation
Fault LED, Green
Normal Mode
ON
Control is Non-functional
OFF
Test Mode
Slow Flash
Lockout Active
Fast Flash
Dehumidification Mode
Flash Code 2
Load Shed
Flash Code 5
Emergency Shutdown
Flash Code 6
On Peak Mode
Flash Code 7
(Future Use)
Flash Code 8
(Future Use)
Flach Code 9
Configuration LED (LED2, Yellow)
Description of Operation
Configuration LED, Yellow
No Software Overwritten
ECM Setting
DIP Switch Overwritten
Slow Flash
ECM Configuration Mode
Fast Flash
Reset Configuration Mode
OFF
Aurora Base or Advanced Control Configuration and
Status Codes
9. Alarm Relay – The Alarm relay (ALM) is factory
connected to 24 VAC via jumper JW2. By cutting JW2,
ABC ALM becomes a dry contact connected to ABC
ALG. The Relay is field switchable between Factory
setting as an Alarm output or available for other uses.
10. Accessory Relay1 – A configurable, accessory relay
on the ABC is provided that can be cycled with the
compressor, blower, or the Dehumidifier (DH) input.
A third (factory) setting cycles the relay with the
compressor but delays the compressor and blower
output for 90 sec. Source pump or slow opening
solenoid valves in well systems or variable speed
primary pumping systems would be a prime use of
this feature.
Access Relay Operation
SW2-4
SW2-5
Cycle with Blower
ON
ON
Cycle with Compressor
OFF
OFF
Water Valve Slow Opening
ON
OFF
Cycle with Comm. T-stat Hum Cmd
OFF
ON
11. Electric Heat EH1 – A digital 24VDC output is provided
for electric heat powering. UPC’s Default programming
has EH1 set for AUX/ELEC Heat operation and will be
controlled using the UPC’s internal P.I.D. logic. However
it can be changed by the BAS to be network controlled.
12. Electric Heat EH2 – A digital VDC output is provided
for field options converted from the original EH2
output. Default UPC program has the EH2 output set
for Network Control but can be changed by the BAS
to be controlled by the UPC’s internal P.I.D. logic.
Controls - UPC DDC Control (optional) cont.