beautypg.com

Controls - upc ddc control (optional) cont – WaterFurnace Versatec Ultra User Manual

Page 39

background image

39

VERSATEC ULTRA SERIES INSTALLATION MANUAL

Status LED (LED3, Green)

Description of Operation

Fault LED, Green

Normal Mode

ON

Control is Non-functional

OFF

Test Mode

Slow Flash

Lockout Active

Fast Flash

Dehumidification Mode

Flash Code 2

Load Shed

Flash Code 5

Emergency Shutdown

Flash Code 6

On Peak Mode

Flash Code 7

(Future Use)

Flash Code 8

(Future Use)

Flach Code 9

Configuration LED (LED2, Yellow)

Description of Operation

Configuration LED, Yellow

No Software Overwritten

ECM Setting

DIP Switch Overwritten

Slow Flash

ECM Configuration Mode

Fast Flash

Reset Configuration Mode

OFF

Aurora Base or Advanced Control Configuration and

Status Codes

9. Alarm Relay – The Alarm relay (ALM) is factory

connected to 24 VAC via jumper JW2. By cutting JW2,

ABC ALM becomes a dry contact connected to ABC

ALG. The Relay is field switchable between Factory

setting as an Alarm output or available for other uses.

10. Accessory Relay1 – A configurable, accessory relay

on the ABC is provided that can be cycled with the

compressor, blower, or the Dehumidifier (DH) input.

A third (factory) setting cycles the relay with the

compressor but delays the compressor and blower

output for 90 sec. Source pump or slow opening

solenoid valves in well systems or variable speed

primary pumping systems would be a prime use of

this feature.

Access Relay Operation

SW2-4

SW2-5

Cycle with Blower

ON

ON

Cycle with Compressor

OFF

OFF

Water Valve Slow Opening

ON

OFF

Cycle with Comm. T-stat Hum Cmd

OFF

ON

11. Electric Heat EH1 – A digital 24VDC output is provided

for electric heat powering. UPC’s Default programming

has EH1 set for AUX/ELEC Heat operation and will be

controlled using the UPC’s internal P.I.D. logic. However

it can be changed by the BAS to be network controlled.

12. Electric Heat EH2 – A digital VDC output is provided

for field options converted from the original EH2

output. Default UPC program has the EH2 output set

for Network Control but can be changed by the BAS

to be controlled by the UPC’s internal P.I.D. logic.

Controls - UPC DDC Control (optional) cont.