Model
Rated
Voltage
Voltage
Min/Max
Compressor
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
LRA**
015
208-230/60/1
187/253
9.2
5.9
29.0
n/a
4.0
9.9
11.4
15
265/60/1
238/292
7.8
5.0
28.0
n/a
4.1
9.1
10.3
15
018
208-230/60/1
187/253
10.4
6.7
33.5
13.4
4.0
10.7
12.4
15
265/60/1
238/292
8.7
5.6
28.0
n/a
4.1
9.7
11.1
15
023
208-230/60/1
187/253
21.0
13.5
58.3
23.3
4.0
17.5
20.9
30
265/60/1
238/292
14.0
9.0
54.0
n/a
4.1
13.1
15.4
20
208-230/60/3
187/253
11.0
7.1
55.0
33.0
4.0
11.1
12.9
15
460/60/3
414/506
5.5
3.5
28.0
16.8
4.1
7.6
8.5
10/15
024
208-230/60/1
187/253
21.0
13.5
58.3
23.3
4.0
17.5
20.9
30
265/60/1
238/292
14.0
9.0
54.0
n/a
4.1
13.1
15.4
20
208-230/60/3
187/253
11.0
7.1
55.0
33.0
4.0
11.1
12.9
15
460/60/3
414/506
5.5
3.5
28.0
16.8
4.1
7.6
8.5
10/15
030
208-230/60/1
187/253
22.0
14.1
73.0
29.2
4.0
18.1
21.6
35
265/60/1
238/292
17.5
11.2
60.0
n/a
4.1
15.3
18.1
25
208-230/60/3
187/253
13.9
8.9
58.0
34.8
4.0
12.9
15.1
20
460/60/3
414/506
6.5
4.2
28.0
16.8
4.1
8.3
9.4
10/15
036
208-230/60/1
187/253
27.0
17.3
96.7
38.7
4.0
21.3
25.6
40
265/60/1
238/292
19.0
12.2
72.0
n/a
4.1
16.3
19.3
30
208-230/60/3
187/253
20.0
12.8
95.0
57.0
4.0
16.8
20.0
30
460/60/3
414/506
10.0
6.4
45.0
27.0
4.1
10.5
12.1
15
041
208-230/60/1
187/253
31.0
20.0
115.0
46.0
4.0
24.0
29.0
45
208-230/60/3
187/253
20.0
12.8
95.0
57.0
4.0
16.8
20.0
30
460/60/3
414/506
10.0
6.4
45.0
27.0
4.1
10.5
12.1
15
042
208-230/60/1
187/253
31.0
20.0
115.0
46.0
4.0
24.0
29.0
45
208-230/60/3
187/253
20.0
12.8
95.0
57.0
4.0
16.8
20.0
30
460/60/3
414/506
10.0
6.4
45.0
27.0
4.1
10.5
12.1
15
042*
208-230/60/1
187/253
31.0
20.0
115.0
46.0
7.0
27.0
32.0
50
208-230/60/3
187/253
20.0
12.8
95.0
57.0
7.0
19.8
23.0
35
460/60/3
414/506
10.0
6.4
45.0
27.0
6.9
13.3
14.9
20
048
208-230/60/1
187/253
32.0
21.0
115.0
46.0
4.0
25.0
30.3
50
208-230/60/3
187/253
25.0
16.0
115.0
69.0
4.0
20.0
24.0
40
460/60/3
414/506
12.0
7.7
50.0
30.0
4.1
11.8
13.7
20
048*
208-230/60/1
187/253
32.0
21.0
115.0
46.0
7.0
28.0
33.3
50
208-230/60/3
187/253
25.0
16.0
115.0
69.0
7.0
23.0
27.0
40
460/60/3
414/506
12.0
7.7
50.0
30.0
6.9
14.6
16.5
20
060
208-230/60/1
187/253
41.0
26.3
150.0
60.0
7.0
33.3
39.9
60
208-230/60/3
187/253
27.5
17.6
120.0
72.0
7.0
24.6
29.0
45
460/60/3
414/506
13.0
8.3
70.0
42.0
6.9
15.2
17.3
25
070
208-230/60/1
187/253
47.0
30.1
145.0
58.0
7.0
37.1
44.6
70
208-230/60/3
187/253
28.0
17.3
120.0
72.0
7.0
24.9
29.4
45
460/60/3
414/506
15.0
9.6
70.0
42.0
6.9
16.5
18.9
25
05/21/13