Vii. command line interface (cli) protocol, Prompts, Control commands – SurgeX CM-1115-RT-AR User Manual
Page 19: Device commands
CM-1115(20)-RT-AR User Manual
Page 18
VII. Command Line Interface (CLI) Protocol
The Command Line Interface provides complete setup of all functions of the AR. The CLI may be accessed through the Telnet protocol,
and requires a Telnet client program. Some commands of the CLI require administrative rights; these are indicated in the following tables.
Prompts
Prompt
Description
User>
Prompts the user to enter the user name (either user or admin).
Password>
Prompts the user to enter the password.
SX-iPD>
Prompt displayed while logged in.
SX-iPD Reboot Required>
Prompt displayed after changes have been made that require a reboot.
This prompt will remain active until the AR has been rebooted.
Control Commands
Command
Description
Admin
Fact Def
get outlet
Returns the current status of the outlet.
No
set outlet < on | off | cycle >
Sets the outlet to the selected state.
No
Device Commands
Command
Description
Admin
Fact Def
get location
Returns the location ID.
Yes
New SX-iPD
set location < 20 character max >
Sets the location ID.
Yes
get cycle
Returns the cycle time currently in use in seconds.
Yes
10
set cycle < 1-999 >
Sets the cycle time in seconds.
Yes
get upgrade enable
Returns the upgrade enable status.
No
Disabled
set upgrade enable < yes | no >
Enables or disables the ability to upload new
f
Yes
logout
Terminates the telnet session.
No
reboot
Reboots the AR.
Yes