CM-1115(20)-RT-AR User Manual

Page 15


VI. Web Server

(continued)

• Action: Select the action to be triggered.

None

AutoPing not used

Power On – Latch

Upon triggering, AR will power on and remain so until
changed via web, telnet, or DxP.

Power On – Follow

Upon triggering, AR will power on. When the ping
response returns, AR will power off.

Power Off – Latch

Upon triggering, AR will power off and remain so until
changed via web, telnet, or DxP.

Power Off – Follow

Upon triggering, AR will power off. When the ping
response returns, AR will power on.

Power Cycle

Upon triggering, AR will cycle the power. AR will then wait
for (Ping Frequency x Fail Count) seconds; if the
response does not return, the power will be cycled again.
This will repeatedly continue until the ping response
returns or AutoPing is turned off. Ensure that the
AutoPing frequency is longer than the time required to
reboot the device.

Power Cycle - Once

Upon triggering, AR will cycle power one time. It will not
cycle again automatically until the ping response returns
and is lost again.