Environmental Tests
Industry Standards
Test Level Limits
Radiated RF immunity
(Performance Criteria A)
IEC 61000-4-3: Level 3
10 V/M with 1 kHz sine wave 80%
AM from 80 MHz to 2000 MHz
10 V/M with 200 Hz sine wave
50% Pulse 100% AM at 900
MHz
10 V/M with 200 Hz sine wave
50% Pulse 100% AM at
1890 MHz
1 V/M with 1 kHz sine wave 80%
AM from 2000 MHz to 2700
MHz
EFT/B immunity
(Performance Criteria B)
IEC 61000-4-4
Signal Ports:
±3 kV at 5 kHz for 5 minutes
Criteria B
±2 kV at 5 kHz for 5 minutes
Criteria A
±2 kV at 5 kHz for 5 minutes
Criteria B (standard)
Power Ports:
±2 kV at 5 kHz for 5 minutes
Criteria A
±2 kV at 5 kHz for 5 minutes
Criteria B (standard)
Surge transient immunity
(Performance Criteria B)
IEC 61000-4-5
Signal Ports:
±2 kV line-earth {CM}at 2 Ω on
shielded ports
Power Ports
±2 kV CM @ 12 Ω
±1 kV DM @ 2 Ω
Conducted RF immunity
(Performance Criteria A)
IEC 61000-4-6
10 V RMS with 1 kHz sine wave
80% AM from 150 kHz to 80
MHz on signal and power ports
Magnetic field
(Performance Criteria A)
IEC 61000-4-8
30 Arms/m
AC mains voltage dips,
interruptions, and
variations
IEC 61000-4-11
Follow the 61000-4-11