6 devicenet object, 7 assembly object, 6 devicenet object -6 – Spectrum Controls 1734sc-OE2CIH User Manual
Page 42: 7 assembly object -6
4-6
Chapter 4: OE2CIH and HART
User’s Manual Pub. 0300272-01 Rev. A.0
4.2.6 DeviceNet Object
This object class configures port attributes such as baud rate and MAC ID.
Table 4-4 Device Net Object
Class Code:
0×03
Instances:
#1
Class Attributes:
None
Class Services:
None
Instance Attributes:
Attr
Name (Data Type) Value
G/S
Description
1
MAC ID (USINT)
0-63
G
The current MAC ID
2
Baud (USINT)
3
G
Baud rate.
The baud is fixed at 1 Mbps and
cannot be changed. The official
DeviceNet specification only
supports values 0 to 2 but since this
module uses a non-standard baud,
we use 3.
Instance Services:
Code
Service Name
Description
14 0×0E
Get Single
Read the value of the attribute
4.2.7 Assembly Object
The 1734sc-OE2CIH module will have one configuration assembly, two input
assemblies, and one output assembly. Multiple instances of input assemblies allow the
user to optimize system performance by limiting the produced data to that which is
needed. Input assembly options allow the user to select status only for maximum
throughput status + HART data for both channels. The AOP used for initial release will
support only the Status + All Hart Channels Instance #103.