This appendix contains configuration information as follows:
Table A-1 Environmental Specifications
Environmental Tests
Industry Standards
Test Level Limits
Temperature (Operating)
(Performance Criteria A)
IEC60068-2-1: (Test Ad, Operating Cold),
IEC60068-2-2: (Test Bd, Operating Dry Heat),
IEC60068-2-14: (Test Nb, Operating Thermal
Shock)
0°C to 55°C (-4°F to 131°F)
(natural convection cooling)
Temperature
(Non-operating)
(Performance Criteria B)
IEC60068-2-1:
(Test Ab, Unpackaged Non-operating Cold),
IEC60068-2-2:
(Test Bb, Unpackaged Non-operating Dry Heat),
IEC60068-2-14:
(Test Na, Unpackaged Non-operating Thermal
Shock)
-40°C to +85°C (-40°F to 185°F)
Humidity (Operating)
(Performance Criteria A)
IEC60068-2-30:
(Test Db, Unpackaged Damp Heat):
5% to 95% non-condensing
Vibration (Operating)
(Performance Criteria A)
IEC60068-2-6: (Test Fc, Operating)
10 Hz to 500 Hz, 5g
Shock (Operating)
(Performance Criteria A)
IEC60068-2-27: (Test Ea, Unpackaged Shock)
30 g, 11 ms half sine (3 mutually
perpendicular axes)
Shock (Non-operating)
(Performance Criteria B)
IEC60068-2-27: (Test Ea ,Unpackaged Shock)
50g, 11 ms half sine (3 mutually
perpendicular axes)
Radiated Emissions
CSIPR 11; Group 1, Class A
(Enclosure) Class A, 30 MHz to 1
GHz
Conducted Emissions
IEC 61000-6-4:2007
Group 1, Class A (AC Mains)
150 kHz to 30 MHz
ESD immunity
(Performance Criteria B)
IEC 61000-4-2
6 kV Indirect (Coupling Plate)
6 kV Contact Discharge (to points
of initial contact)
8 kV Air Discharge (to points of
initial contact)